The choice of fuse is mainly based on the protection characteristics of the load and the size of the short-circuit current to select the type of fuse. For small-capacity motors and lighting branch lines, fuses are often used as overload and short-circuit protection, so the melting coefficient of the melt is expected to be appropriately small.
RQA series fuses of lead-tin alloy melt are usually selected. For larger-capacity motors and lighting trunks, short-circuit protection and breaking capacity should be considered emphatically. RM10 and RL1 series fuses with higher breaking capacity are usually selected; when the short-circuit current is large, RT0 and RTl2 series fuses with current limiting function should be used.
Type | HRW7 | HRW7 |
Rated Voltage (kV) | 12 | 12 |
Rated Current (A) | 100 | 200 |
Breaking Current (A) | 6300 | 12500 |
Impulse Voltage (BIL) | 125 | 125 |
Power frequency withstand Voltage (kV) | 45 | 45 |
Leakage distance (mm) | 380 | 380 |
Weight (kg) | 4.5 | 4.7 |
Dimensions (cm) | 46*35*26 |